Wago Fieldbus Coupler - DeviceNet ECO 125...500 Kbaud |
|
Part Number |
Conformity Marking |
Approvals |
750-346 |
|
cULus, cULus-EX, KEMA |
DeviceNet ECO FIELDBUS COUPLER 125-500 kBaud CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The ECO fieldbus coupler is designed for applications with a reduced scale I/O requirement. Using digital only process data or small amounts of analogs, while retaining all of the choice thats offered by the Series 750 I/O. The coupler has an integrated supply terminal for the system voltage. The field power jumper contacts are supplied via a separate supply module. The DeviceNet bus coupler is capable of supporting all I/O modules and automatically configures, creating a local process image. DeviceNet allows the storing of the process image in the corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the DeviceNet fieldbus to the PLC, PC or NC for further processing, and received from the field via DeviceNet.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte. Note: EDS files required |
|
Technical Information |
Characteristic |
Value |
Max. no. of nodes |
64 with scanner |
Max. no. Of I/O points |
ca. 6000 (depends on Master) |
Transmission medium |
shielded Cu- cabletrunk line: 2 x 0.82mm² + 2 x 1.7 mm²drop line: 2 x 0.2mm² + 2 x 0.32 mm² |
Max. length of fieldbus segment |
100 m ... 500 m (depends on the baud rate / on the cable) |
Baud rate |
125 kBaud, 250 kBaud, 500 kBaud |
Buscoupler connection |
5-POLE MALE CONNECTOR, SERIES 231 (MCS); CONNECTOR 231-305/010-000/050-000 IS INCLUDED |
UL 508 |
E175199, UL 508 |
Conformity marking |
CE |
Max. no. of I/O modules |
64 |
Max. fieldbus input image (Byte) |
32 Byte |
Max. fieldbus output image (Byte) |
32 Byte |
Configuration |
via PC or PLC |
Voltage supply |
DC 24 V (-15% / + 20%) |
Current consumption using a power supply |
260 mA / 24 V |
Power consumption via CAN interface |
< 120 mA / 11 V |
Efficiency of the power supply |
80% |
Internal current consumption |
350 mA |
|
Characteristic |
Value |
Total current for the I/O modules |
650 mA |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
gem. EN 50082-2 (1996), EN 61000-6-2 (1999) |
EMC emission of interference |
acc. EN 50081-2 (94) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
1.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Weight |
115 g |
Color |
light gray |
Height |
65 mm |
Height |
2.56 in |
Width |
50 mm |
Width |
1.969 in |
Depth |
97 mm |
Depth |
3.819 in |
Strip length from |
5 mm |
Strip length to |
6 mm |
Strip length |
0.22 in |
|
|