Wago Fieldbus Coupler - II/O-LIGHTBUS 2.5 Mbaud |
|
Part Number |
Conformity Marking |
Approvals |
750-320 |
|
cULus, cULus-EX, KEMA |
II/O-LIGHTBUS FIELDBUS COUPLER 2.5 MBaud CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
This buscoupler allows connection of the WAGO-I/O-SYSTEM as a slave to the LIGHTBUS fieldbus.The buscoupler automatically configures, creating a local process image which may include analog, digital or specialty modules.
The data of the modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte. |
|
Technical Information |
Characteristic |
Value |
Max. no. of nodes |
254 |
Max. no. Of I/O points |
16192 |
Transmission medium |
LWL, APF or HCS |
Max. length of fieldbus segment |
45 m (APF); 300 m (HCS) |
Baud rate |
2.5 Mbaud |
Transmission time |
1 ms (10 Modules; 32 I, 32 O/Mod) |
Buscoupler connection |
2 x fibre optic cable Z1000 (APF) Z1010 (HCS) |
UL 508 |
E175199, UL 508 |
UL 1604 |
E198726, UL 1604 Class 1 Dev2 ABCD T4A |
KEMA |
01ATEX1024X Eex nA II T4 |
Conformity marking |
CE |
Max. no. of I/O modules |
64 |
Max. fieldbus input image (Byte) |
512 Byte |
Max. fieldbus output image (Byte) |
512 Byte |
Configuration |
via PC or PLC |
Voltage supply |
DC 24 V (-15% / + 20%) |
Input current (max) |
500 mA |
Efficiency of the power supply |
87% |
Internal current consumption |
350 mA |
Total current for the I/O modules |
1650 mA |
Isolation |
500 V system / supply |
Voltage via power jumper contacts (max) |
DC 24 V (-15% / + 20%) |
|
Characteristic |
Value |
Current via power jumper contacts (max) |
DC 10 A |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
acc. EN 50081-2 (94) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Voltage CSA |
24 V |
Color |
light gray |
Height |
65 mm |
Height |
2.56 in |
Width |
51 mm |
Width |
2.008 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|