Wago Fieldbus Coupler - INTERBUS Fiber Optic |
|
Part Number |
Standard |
Cert. |
Conformity Marking |
Approvals |
750-334 |
EN 50254 |
INTERBUS CLUB |
|
cULus, ABS*, BV*, DNV*, GL*, LR*, RINA*, cULus-EX, KEMA |
750-626 filter module is absolutely necessary |
INTERBUS FIELDBUS COUPLER DIGITAL AND ANALOG SIGNALS CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
This buscoupler connects the WAGO-I/O-SYSTEM as a slave to the INTERBUS fieldbus.
The buscoupler automatically configures, creating a local process image which may include analog, digital or specialty modules. Analog and specialty data is sent via words abd/or bytes, digital data is sent bit by bit.
INTERBUS stores the process image in the corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the INTERBUS fieldbus to the PLC, PC or NC for further processing, and received from the field via INTERBUS.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte.
The fiber optic INTERBUS coupler can be put in any place on the ring.
|
|
Technical Information |
Characteristic |
Value |
Max. no. of nodes |
256 |
Max. no. Of I/O points |
4096 (depends on Master) |
Transmission medium |
APF 1000?m |
Max. length of fieldbus segment |
1 m ... 40 m |
Topology |
ring, double fiber ring |
Data transmission rate (kBaud) |
500 kBaud |
Buscoupler connection |
F- SMA |
UL 508 |
E175199, UL 508 |
Standard |
EN 50254 |
Certification |
INTERBUS CLUB |
Conformity marking |
CE |
Max. no. of I/O modules |
64 |
Max. fieldbus input image (Byte) |
64 Byte |
Max. fieldbus output image (Byte) |
64 Byte |
Configuration |
via PC or PLC |
Voltage supply |
DC 24 V (-15% / + 20%) |
Input current (max) |
500 mA |
Efficiency of the power supply |
87% |
Internal current consumption |
350 mA |
Total current for the I/O modules |
1650 mA |
Isolation |
500 V system / supply |
Voltage via power jumper contacts (max) |
DC 24 V (-15% / + 20%) |
Current via power jumper contacts (max) |
DC 10 A |
|
Characteristic |
Value |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
acc. EN 50081-2 (94) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Voltage CSA |
24 V |
Weight |
202 g |
Color |
light gray |
Height |
65 mm |
Height |
2.56 in |
Width |
51 mm |
Width |
2.008 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|