Wago Fieldbus Coupler - PROFIBUS DP/FMS 12 Mbaud |
|
Part Number |
Standard |
Cert. |
Conformity Marking |
Approvals |
750-303 |
EN 50170 |
PNO |
|
cULus, ABS*, BV*, DNV*, GL*, LR*, RINA*, cULus-EX, KEMA |
750-626 filter module is absolutely necessary |
PROFIBUS DP/FMS FIELDBUS COUPLER 12 MBaud CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
This buscoupler allows connection of the WAGO-I/O-SYSTEM as a slave to the PROFIBUS fieldbus.
The buscoupler is capable of supporting all I/O modules. The buscoupler automatically configures, creating a local process image which may include analog, digital or specialty modules. Analog and specialty module data is sent via words and/or bytes, digital data is sent bit by bit.
PROFIBUS allows the storing of the process image in the corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the PROFIBUS fieldbus to the PLC, PC or NC for further processing, and received from the field via PROFIBUS.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte.
When implementing new installations with PROFIBUS DP, please consider fieldbus coupler
750-333 with extended functions (page 1.020). Note: GSD files required |
|
Technical Information |
Characteristic |
Value |
Max. no. of nodes |
96 with repeater |
Max. no. Of I/O points |
ca. 6000 (depends on Master) |
Transmission medium |
Cu-cable acc. to EN 50170 |
Max. length of fieldbus segment |
100 m ... 1200 m (depends on the baud rate / on the cable) |
Baud rate |
9.6 kBaud ... 12 Mbaud |
Transmission time |
typ. 1 ms (10 Modules; 32 E, 32 A/Mod;at 12 Mbaud and digital Signals)max. 3.3 ms |
Buscoupler connection |
1 x D-SUB 9; socket |
UL 508 |
E175199, UL 508 |
UL 1604 |
E198726, UL 1604 Class 1 Dev2 ABCD T4A |
KEMA |
01ATEX1024X Eex nA II T4 |
Standard |
EN 50170 |
Certification |
PNO |
Conformity marking |
CE |
Max. no. of I/O modules |
64 |
Max. fieldbus input image (Byte) |
128 Byte |
Max. fieldbus output image (Byte) |
128 Byte |
Configuration |
via PC or PLC |
Voltage supply |
DC 24 V (-25% / + 30%) |
Input current (max) |
500 mA |
Efficiency of the power supply |
87% |
Internal current consumption |
350 mA |
Total current for the I/O modules |
1650 mA |
Isolation |
500 V system / supply |
Voltage via power jumper contacts (max) |
DC 24 V (-25% / + 30%) |
|
Characteristic |
Value |
Current via power jumper contacts (max) |
DC 10 A |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
acc. EN 50081-2 (94) |
EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
EMC marine applications - noise transmission |
gem. Germanischer Lloyd (1997) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Voltage CSA |
24 V |
Weight |
226 g |
Color |
light gray |
Height |
65 mm |
Height |
2.56 in |
Width |
51 mm |
Width |
2.008 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
Weight |