Connex-Electronics.com
NK Technologies
NK Technologies - ATR Series, AC Current Transducers, True RMS
   
Back to NK Technologies Main Selection Page
AC and DC Current Switches
AS1 Series, Single-Range AC Current Switch
AS1 DODC Series, Current Switch with Dual Output
AS3 Series, Multi-Range AC Current Operated Switches
ASM Series, Self-Calibrating AC Current Switches
ASX Series, AC Current Switches with Time Delay
ASXP Series, Powered AC Current Switches with Time Delay
AS0 Series, Low Range AC Current Operated Switches
DS3 Series, DC Current Operated Switches
AC and DC Current Transducers
AT Series, AC Current Transducers, Average Responding
ATR Series, AC Current Transducers, True RMS
AT/ATR 3 & 4 Series, High Current AC Transducers
ATP Series, Powered AC Current Transducers
ATP/ATPR 3 & 4 Series, Powered AC Current Transducers, True RMS
DT Series, DC Current Transducers
Ground Fault / Earth Leakage Sensors
AG Series, Ground Fault/Earth Leakage Sensors - Solid-State Relay Output
AG Series, Ground Fault/Earth Leakage Sensors - Mechanical Relay Output
AGL Series, Large Aperture Ground Fault Sensors
ATR Series, AC Current Transducers, True RMS
 
ATR Series Current Transducers combine a current transformer and a True RMS signal conditioner into a single package. The ATR Series provides True RMS output on distorted waveforms found on VFD or SCR outputs, and on linear loads in “noisy” power environments. Available in a solidor split-core case. NK Technologies ATR Series
Download Complete Specifications in .pdf Format
Applications :
VFD Controlled Loads
Monitoring VFD output indicates how the motor and attached load are operating.
SCR Controlled Loads
  • Accurate measurement of phase angle fired or burst fired (time proportioned) SCRs.
  • Current measurement gives faster response than temperature measurement.
Switching Power Supplies and Electronic Ballasts
True RMS sensing is the most accurate way to measure power supply or ballast input power.
Features:

  • True RMS Output - True RMS technology is accurate on distorted waveforms like VFD or SCR ouputs.
  • Jumper Selectable Ranges
    • Reduces inventory.
    • Eliminates zero and span pots.
  • Isolation
    • Output is magnetically isolated from the input for safety.
    • Eliminates insertion loss (voltage drop).
  • UL, CUL and CE Approval - Accepted worldwide.
 
Download Complete Specifications in .pdf Format
Specifications:
Output Signal 4–20mA, Loop-powered, True RMS
Output Limit 23mA
Accuracy 1.0% FS
Response Time (10–90% step change) 600 ms (to 90% step change)
Frequency Range 10–400Hz
Power Supply 24VDC Nominal, 40VDC Maximum
Isolation Voltage UL listed to 1,270VAC (tested to 5KV)
Input Ranges Field selectable ranges from 0–200A; custom ranges available; consult factory.
Sensing Aperture
  • -FT Case: 0.74” (19mm) dia.
  • -SP Case: 0.85” (21.6mm) sq.
Case UL94 V0 Flammability Rated
Environmental -4 to 122°F (-20 to 50°C) 0–95% RH, noncondensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE
.
   
Ordering Information Download Complete Specifications in .pdf Format
Solid-Core Models
Model Description Output
Add part number ATR0-420-24L-FT to your Quote. ATR0-420-24L-FT 0–2 & 0–5A Ranges, Top Term. 4–20mA True RMS
Add part number ATR1-420-24L-FT to your Quote. ATR1-420-24L-FT 0–10, 0–20, 0–50A Ranges, Top Term. 4–20mA True RMS
Add part number ATR2-420-24L-FT to your Quote. ATR2-420-24L-FT 0–100, 0–150, 0–200A Ranges, Top Term. 4–20mA True RMS
Split-Core Models
Model Description Output
Add part number ATR0-420-24L-SP to your Quote. ATR0-420-24L-SP 0–2 & 0–5A Ranges 4–20mA True RMS
Add part number ATR1-420-24L-SP to your Quote. ATR1-420-24L-SP 0–10, 0–20, 0–50A Ranges 4–20mA True RMS
Add part number ATR2-420-24L-SP to your Quote. ATR2-420-24L-SP 0–100, 0–150, 0–200A Ranges 4–20mA True RMS