Connex-Electronics.com
NK Technologies
NK Technologies - ASM Series, Self-Calibrating Current Switches
   
Back to NK Technologies Main Selection Page
AC and DC Current Switches
AS1 Series, Single-Range AC Current Switch
AS1 DODC Series, Current Switch with Dual Output
AS3 Series, Multi-Range AC Current Operated Switches
ASM Series, Self-Calibrating AC Current Switches
ASX Series, AC Current Switches with Time Delay
ASXP Series, Powered AC Current Switches with Time Delay
AS0 Series, Low Range AC Current Operated Switches
DS3 Series, DC Current Operated Switches
AC and DC Current Transducers
AT Series, AC Current Transducers, Average Responding
ATR Series, AC Current Transducers, True RMS
AT/ATR 3 & 4 Series, High Current AC Transducers
ATP Series, Powered AC Current Transducers
ATP/ATPR 3 & 4 Series, Powered AC Current Transducers, True RMS
DT Series, DC Current Transducers
Ground Fault / Earth Leakage Sensors
AG Series, Ground Fault/Earth Leakage Sensors - Solid-State Relay Output
AG Series, Ground Fault/Earth Leakage Sensors - Mechanical Relay Output
AGL Series, Large Aperture Ground Fault Sensors
NK Technologies - ASM Series, Self-Calibrating Current Switches
 
ASM Series Load Monitoring Switches are designed for overload, underload or operating window applications. Upon sensing an average operating current, the ASM self-learns and establishes a limit-alarm trip point based on +/- 15% of the average expected current draw. The ASM is available in solid- or splitcore enclosure styles. NK Technologies ASM Series
Download Complete Specifications in .pdf Format
Applications :
Electronic Proof of Flow (-UL option)
  • No need for pipe or duct penetrations.
  • More reliable than electro-mechanical pressure or flow switches.
Conveyors (-OL option)
  • Detects jams and overloads.
  • Interlocks multiple conveyor sections.
Lighting or Heating Circuits (-UL option)
Fast and easy installation.
Pump Protection (-OU option)
Provides overload (jams) and underload (suction loss) indication.
Features:

  • Self-powered and Self-calibrating - Speeds start-ups, cuts installation costs.
  • Status Monitoring, Overload, and Operating Window Options - Choose the operating style that matches your application.
  • Universal Output - AC or DC compatibility with any automation system.
  • UL, CUL and CE Approval - Accepted worldwide.
 
Download Complete Specifications in .pdf Format
Specifications:
Power Supply None — Self-powered
Output Magnetically Isolated Solid-State Switch
Output Rating Max.
  • N.O. Version: 0.30A @ 135 VAC or VDC
  • Not polarity sensitive
Off State Leakage <10µA
Response Time 200ms
Setpoint Range
  • Solid-core: 1.5&#150;150A
  • Split-core: 2.8&#150;150A
Hysteresis 5% of Setpoint
Overload 500A @ 6sec., 1,000A @ 1sec.
Isolation Voltage UL Listed to 1,270VAC, tested to 5,000VAC
Frequency Range 6–100Hz
Setpoint
  • Overload: +15% of Load (-OL)
  • Underload: -15% of Load (-UL)
  • Operating Window +/- 15% of Setpoint
Case UL 94V-O Flammability Rated
Environmental -58 to 122°F (-50 to 50°C) 0–95% RH, non-condensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE
Dimensions 3.50" x 2.25" x 1.20", Aperture: 0.74"– 0.85"
.
   
Ordering Information Download Complete Specifications in .pdf Format
Solid-Core Models
Model Description Output
Add part number ASM-NOU-OL-FT to your Quote. ASM-NOU-OL-FT 1.5–150A Self Calibrating Setpoint, Overload Only N.O., 0.15A@240VAC
Add part number ASM-NOU-OU-FT to your Quote. ASM-NOU-OU-FT 1.5–150A Self Calibrating Setpoint, Over/Underload N.O., 0.15A@240VAC
Add part number ASM-NOU-UL-FT to your Quote. ASM-NOU-UL-FT 1.5–150A Self Calibrating Setpoint, Underload Only N.O., 0.15A@240VAC
Split-Core Models
Model Description Output
Add part number ASM-NOU-OL-SP to your Quote. ASM-NOU-OL-SP 2.5–150A Self Calibrating Setpoint, Overload Only N.O., 0.15A@240VAC
Add part number ASM-NOU-OU-SP to your Quote. ASM-NOU-OU-SP 2.5–150A Self Calibrating Setpoint, Over/Underload N.O., 0.15A@240VAC