Connex-Electronics.com
NK Technologies
NK Technologies - ASX Series Time-Delay AC Current Switches
   
Back to NK Technologies Main Selection Page
AC and DC Current Switches
AS1 Series, Single-Range AC Current Switch
AS1 DODC Series, Current Switch with Dual Output
AS3 Series, Multi-Range AC Current Operated Switches
ASM Series, Self-Calibrating AC Current Switches
ASX Series, AC Current Switches with Time Delay
ASXP Series, Powered AC Current Switches with Time Delay
AS0 Series, Low Range AC Current Operated Switches
DS3 Series, DC Current Operated Switches
AC and DC Current Transducers
AT Series, AC Current Transducers, Average Responding
ATR Series, AC Current Transducers, True RMS
AT/ATR 3 & 4 Series, High Current AC Transducers
ATP Series, Powered AC Current Transducers
ATP/ATPR 3 & 4 Series, Powered AC Current Transducers, True RMS
DT Series, DC Current Transducers
Ground Fault / Earth Leakage Sensors
AG Series, Ground Fault/Earth Leakage Sensors - Solid-State Relay Output
AG Series, Ground Fault/Earth Leakage Sensors - Mechanical Relay Output
AGL Series, Large Aperture Ground Fault Sensors
NK Technologies - ASX Series Time-Delay AC Current Switches
 
ASX Series Current Operated Switches are high performance current-operated switches with field-adjustable time delay to help minimize nuisance trips during start-up and operation. Designed for motor status applications where setpoint accuracy and repeatability are critical, the ASX Series offers a linear setpoint characteristic and constant hysteresis. Standard features include self-powering, jumper-selectable ranges and a choice of outputs and cases. NK Technologies ASX Series
Download Complete Specifications in .pdf Format
Applications :
Motor Protection
  • Serves as an electronic proof-of-operation; detects current draw changes in motors when they encounter problems such as pumps running dry or pending bearing failure.
  • Non-intrusive, less expensive to install than differential pressure flow sensors or thermal switches.
  • Much quicker response time than Class 10 overload relays.
High Inrush or Temporary Overload Current
Adjustable start-up/delay timer allows 0–15 second delay to eliminate nuisance trips from high inrush or short overload conditions.
Features:

  • Adjustable Start-up/Delay Timer - Field-adjustable from 0–15 seconds to eliminate nuisance alarms due to start-up inrush or temporary overcurrent conditions.
  • Choice of N.O./N.C. AC or Universal Outputs - Contact ratings of 1.0A @ 240VAC or universal outputs of 0.15A @ 240VAC/VDC (N.O. models) and 0.2A @ 135VAC/VDC (N.C. models) for use with most standard motor control systems.
  • Improved Ease of Installation and Use
    • 1.0A AC rating eliminates need for time delay relay.
    • Self-powered, split-core models simplify installation.
    • Status LED provides visual indication of setpoint trip and contract action.
  • Industrial Grade Performance - Constant hysteresis and linear response characteristic enhance setpoint accuracy.
  • Agency Approved - UL listed, CE pending.
 
Download Complete Specifications in .pdf Format
Specifications:
Power Supply None — Self-powered
Output Isolated Solid-State Switch
Output Rating
  • NOAC/NCAC: 1A @ 240VAC
  • NOU: 0.15A @ 240VAC or VDC
  • NCU: 0.2A @ 135VAC or VDC
Off State Leakage <10µA
Response Time Adjustable 0.2 to 15 Seconds
Setpoint Range Jumper Selectable: 1.5–12A, 12–55A, 50–200A
Hysteresis 5% (constant)
Overload
  • 1.5&#150;12A Range: 600A Maximum
  • 12&#150;55A Range: 800A Maximum
  • 50&#150;200A Range: 1,200A Maximum
Isolation Voltage 5,000VAC (tested)
Frequency Range 50–100Hz
Case UL 94V-O Flammability Rated
Environmental 5 to 122°F (-15 to 50°C) 0–95%RH, non-condensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE pending.
.
   
Ordering Information Download Complete Specifications in .pdf Format
Solid-Core Models
Model Description Output
Add part number ASX-NOU-FT to your Quote. ASX-NOU-FT Adj. Setpoint 1.5–12, 12–55, and 50–175A N.O., 0.15A@240VAC
Add part number ASX-NCU-FT to your Quote. ASX-NCU-FT Adj. Setpoint 1.5–12, 12–55, and 50–175A N.C., 0.2A@135VDC
Add part number ASX-NOAC-FT to your Quote. ASX-NOAC-FT Adj. Setpoint 1.5–12, 12–55, and 50–175A N.O., 1A@240VAC
Add part number ASX-NCAC-FT to your Quote. ASX-NCAC-FT Adj. Setpoint 1.5–12, 12–55, and 50–175A N.C., 1A@240VAC
Split-Core Models
Model Description Output
Add part number ASX-NCU-SP to your Quote. ASX-NCU-SP Adj. Setpoint 2–12, 12–55, and 50–200A N.C., 0.2A@135VDC
Add part number ASX-NOU-SP to your Quote. ASX-NOU-SP Adj. Setpoint 2–12, 12–55, and 50–200A N.O., 0.15A@240VAC
Add part number ASX-NOAC-SP to your Quote. ASX-NOAC-SP Adj. Setpoint 2–12, 12–55, and 50–200A N.O., 1A@240VAC
Add part number ASX-NCAC-SP to your Quote. ASX-NCAC-SP Adj. Setpoint 2–12, 12–55, and 50–200A N.C., 1A@240VAC