ASXP Series, Powered AC Current Switches with Time Delay |
|
ASXP Series Current Operated Switches are powered versions of our popular current switches with integral time delay. A fixed two-second delay upon trip minimizes nuisance alarms during start-up and operation in motor or heater status applications. After startup a second 015 second delay can be set. For use with 24VAC/DC or 120VAC supplies, this high performance product offers OEM-caliber accuracy, precision tolerances, low hysteresis and low (non-sinusoidal) frequency operation. Available with status LED and solid-core enclosure as standard. |
|
Download Complete Specifications in .pdf Format |
Motor Protection
- Serves as an electronic proof-of-operation;
detects current draw changes in motors when they encounter problems such as
pumps running dry or pending bearing failure.
- Non-intrusive, less expensive to install
than differential pressure flow sensors or thermal switches.
- Much quicker response time than Class 10
overload relays.
|
High Inrush or Temporary Overload Current Factory-set two-second delay on startup eliminates nuisance trips from high inrush or short overload conditions. After startup, a second 0-15 second delay can be added. |
|
- Fixed Start-up/Delay Timer - Factory
calibrated trip timer set to 2 seconds to eliminate nuisance alarms due to
start-up inrush or temporary overcurrent conditions.
- Choice of N.O./N.C. Electro-mechanical
Relay Output - Contact rating of 10A @ 240VAC provides adequate switching
capacity for use with most motor control systems.
- Improved Ease of Installation and Use
- Eliminates need for separate time delay
relay.
- Choice of 24VAC/DC or 120VAC/DC supply
models.
- LED provides indication of trip point
contact status.
- Setpoint adjustable from
1–50A.
- Industrial Grade Performance - 0.5% accuracy, precise time delay setpoint, constant hysteresis, linear response and low frequency capability.
|
|
|
|
Power Supply |
24VAC/DC or 120VAC/VDC, (+/- 10%), 2VA max |
Output |
Electromechanical SPST Relay, Auto Reset |
Output Rating |
10A @ 240VAC |
Trip Point Range |
- ASXP1: 1–20A
- ASXP2: 20–50A
|
Time Delay |
2.0 sec (fixed on startup) 0-15 sec (adjustable after startup) |
Maximum Inrush Current |
500A (5 second duration) |
Hysteresis |
5% (constant) |
Isolation Voltage |
1,250 VAC (monitored) |
Frequency Range |
6100Hz |
Sensing Aperature |
0.75 (19.1mm) dia. |
Case |
UL94 V0 Flammability Rated |
Environmental |
-4 to 122oF (-20 to 50oC) 095%RH, non-condensing |
. |
|
|
|
Ordering Information |
Download Complete Specifications in .pdf Format |
Solid-Core Models Only |
Model |
Description |
Output |
ASXP1-NOR-120-FL |
020A Range, 120VAC Pwr, N.O. w/solid-core |
N.O. SPST 10A@240VAC |
ASXP1-NCR-120-FL |
020A Range, 120VAC Pwr, N.O. w/solid-core |
N.C. SPST 10A@240VAC |
ASXP2-NOR-120-FL |
2050A range, 120VAC Pwr, N.C. w/solid-core |
N.O. SPST 10A@240VAC |
ASXP2-NOR-120-FL |
2050A range, 120VAC Pwr, N.C. w/solid-core |
N.C. SPST 10A@240VAC |
|