Part Number Conformity Marking Approvals
Add part number 750-523 to your Quote. 750-523 CE cULus
1-CHANNEL RELAY OUTPUT MODULE RELAY 1a POTENTIAL FREE CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION
A connected actuator or load is switched via the relay output module. The DC 24 V supply is derived from the power jumper contacts to trigger the relays. The switched status of the relay is shown by the manual switch (1/0). The operating mode can be selected using the manual /automatic switch. The mode status is indicated by a LED and via status bits in the process image.
Manual:
Coil triggering is interrupted. Operation is only possible via the red manual switch.
Auto:
The relay is operated via the control system. Manual status transitions via the manual switch are reset by the control system after less than 500ms.
The manual witch can also be used without 24 V supply to switch the output ON. The relay meets both international standards of IEC and DIN EN 61810 part 1 /VDE 0435 part 201 as well as overload and short circuit requirements of IEC and DIN EN 61036 /61037.
Technical Information
Characteristic Value
Number of outputs 1 MAKE CONTACTS
CURRENT CONSUMPTION (INTERNAL) mA 5 mA
Switching voltage AC 440 V
Switching power max. (VA) 5 VA
Switching current (max) AC 16 A
Current consumption max (field side) 80 mA
Contact material AgSnO2
Isolation 1.5 kV EFF. (FIELD/SYSTEM), 2.5 kV RATED SURGE VOLTAGE; OVERVOLTAGE CATEGORY III
Mechanical life 10^6
Data size 2 BITS IN (MANUAL STATUS, - ); 2 BITS OUT (DO, - )
Operating temperature 0 °C ... + 55 °C
Storage temperature -25 °C ... +85 °C
Relative air humidity 95%
Vibration resistance acc. IEC 60068-2-6
Shock resistance acc. IEC 60068-2-27
Degree of protection IP 20
EMC immunity to interference acc. EN 50082-2 (96)
EMC emission of interference per EN 50081-1 (93)
UL 508 E175199, UL 508
Conformity marking CE
Incandescent lamp (operations 100,000) 1.25 kW
Incandescent lamp (operations 30,000) 2.5 kW
Fluorescent lamp, not compensated (operations 100,000) 1.2 kW
Fluorescent lamp, not compensated (operations 30,000) 2.5 kW
Fluorescent lamp, parallel compensated (operations 100,000) 650 W / 70 ?F
Fluorescent lamp, parallel compensated (operations 30,000) 1,3 kW / 140 ?F
Fluorescent lamp, dual circuit (operations 100,000) 2 x 1,2 kW
Fluorescent lamp, dual circuit (operations 30,000) 2 x 2,5 kW
Halogen lamp (AC 230 V) (operations 100,000) 1.2 kW
Characteristic Value
Halogen lamp (AC 230 V) (operations 30,000) 2.5 kW
Low-voltage halogen lamp with transformer (operations 100000) 500 VA
Low-voltage halogen lamp with transformer (operations 30,000) 500 VA
Mercury arc/sodium-vapor lamp, not compensated (operations 100,000) 1 kW
Mercury arc/sodium-vapor lamp, not compensated (operations 30,000) 2 kW
Mercury arc/sodium-vapor lamp, parallel compensated (operations 100,000) 1 kW / 70 ?F
Mercury arc/sodium-vapor lamp, parallel compensated (operations 30,000) 2 kW / 140 ?F
Duluxe lamp, not compensated (operations 100,000) 800 W
Duluxe lamp, uncompensated (operations 30,000) 1.6 kW
Duluxe lamp, parallel compensated (operations 100,000) 560 W / 70 ?F
Duluxe lamp, parallel compensated (operations 30,000) 1,1 kW / 140 ?F
Cross section from [mm²] 0.08 mm²
Cross section to [mm²] 2.5 mm²
Cross section from [AWG] 28 AWG
Cross section to [AWG] 14 AWG
Weight 105 g
Color light gray
Height 64 mm
Height 2.52 in
Width 24 mm
Width 0.945 in
Depth 100 mm
Depth 3.937 in
Strip length from 8 mm
Strip length to 9 mm
Strip length 0.33 in