Wago Analog Input Modules |
|
Part Number |
Conformity Marking |
750-483 |
|
2-CHANNEL ANALOG INPUT MOUDLE 0-30 V CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The analog input module receives differential signals of values 0V - 30V. The input signal of each channel is electrically isolated and will be transmitted with a resolution of 13 bits. The system supply (via the data bus contacts) is used for the power supply of the module. The shield (screen) is directly connected to the DIN rail. |
|
Technical Information |
Characteristic |
Value |
Number of inputs |
2, ELECTRICALLY ISOLATED FROM EACH OTHER |
Measured-value acquisition |
Time synchronous (both inputs) |
Voltage supply |
via system voltage DC / DC |
Current consumption (mA) |
100 mA |
Signal voltage |
0..30 V |
Internal resistance (kOhm) |
1000 kOhm |
Overrange / measuring range underflow |
Status byte and LED |
Resolution of the A/D converter |
14 Bit |
Measured value cancelled (Bit) |
14 Bit |
Monotonicy without missing codes |
Yes |
Value of a LSB (least significant bit) |
1,8 mV |
Measuring error |
< 0.4 % over whole temperature scale< 0.1 % of upper range value (non-linearity) |
Input filter |
LOW PASS FIRST ORDER, fG = 5 KHZ |
Measuring error (25°) |
< +/- 0.05 % of the full scale value |
Temperature coefficient |
< +/- 0.01 % / K of the full scale value |
UL 508 |
E175199, UL 508 (applied for) |
Crosstalk attenuation |
80 dB |
Sampling time of repetition |
1 ms |
Sampling delay (module) |
1 ms |
Sampling delay (channel/channel) |
1 ?s |
Sampling duration |
5 ?s |
Operating mode |
Triggered (Preset) |
|
Characteristic |
Value |
Method of conversion |
SAR (Successive Approximation Register) |
Protection |
RC-Glied |
Admissible continuous overload |
230 V |
Voltage resistance |
DC 500 V channel / channell bzw. channel / module |
Conformity marking |
CE |
Data size |
2 x 16 Bit Data2 x 8 Bit control / status (optional) |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
per EN 50081-1 (93) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Weight |
55 g |
Color |
light gray |
Height |
64 mm |
Height |
2.52 in |
Width |
12 mm |
Width |
0.472 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|