Connex-Electronics.com
Wago
Wago IO System - Analog Input Modules

Wago Analog Input Modules
Wago 750-469
Part Number Conformity Marking Approvals
Add part number 750-469 to your Quote. 750-469 CE cULus,
ABS, BV, DNV,
GL, LR, RINA,
KEMA
Thermocouple K diag. Add part number 750-469 to your Quote. 750-469
Thermocouple S diag. Add part number 750-469/000-001 to your Quote. 750-469/000-001
Thermocouple T diag. Add part number 750-469/000-002 to your Quote. 750-469/000-002
±120mV diag. Add part number 750-469/000-003 to your Quote. 750-469/000-003
Thermocouple J diag. Add part number 750-469/000-006 to your Quote. 750-469/000-006
Thermocouple E diag. Add part number 750-469/000-008 to your Quote. 750-469/000-008
Thermocouple L diag. Add part number 750-469/000-012 to your Quote. 750-469/000-012
Thermocouple K diag. S5 Add part number 750-469/000-200 to your Quote. 750-469/000-200
Thermocouple J diag. S5 Add part number 750-469/000-206 to your Quote. 750-469/000-206
Thermocouple Free config. Add part number 750-469/003-000 to your Quote. 750-469/003-000
2-CHANNEL ANALOG INPUT MOUDLE TERMOCOUPLE / K / DIAGN. CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION
The thermocouple input module allows the direct connection of two thermocouples. Cold junction compensation is utilized to compensate for the clamping unit offset voltage over the 0 °C ... 55 °C operating range. The module linearizes the entire temperature range automatically. A line break is indicated by a red LED. A green LED indicates readiness for operation and trouble-free communication with the buscoupler. The shield (screen) is directly connected to the DIN rail.
Technical Information
Characteristic Value
No. of inputs 2
Voltage supply via system voltage DC / DC
Current consumption typ (internal) 65 mA
Sensor types TYPE K; -100°C ... +1370°C (FACTORY PRESET), J, B, E, N, R, S, T, U, L
Cold junction compensation at each pair of terminal blocks
Resolution (over the complete area) 0,1 °C
Conversion time 320 MS (BOTH CHANNELS)
Measuring error (25°) < +/- 0.4 % of the full scale value
Temperature coefficient < +/- 0.01 % / K of the full scale value
Isolation 500 V system / supply
Data size 2 x 16 Bit Data2 x 8 Bit control / status (optional)
Operating temperature 0 °C ... + 55 °C
Storage temperature -25 °C ... +85 °C
Relative air humidity 95%
Vibration resistance acc. IEC 60068-2-6
Shock resistance acc. IEC 60068-2-27
Degree of protection IP 20
EMC immunity to interference acc. EN 50082-2 (96)
EMC emission of interference per EN 50081-1 (93)
Characteristic Value
UL 508 E175199, UL 508
EMC marine applications - noise proof gem. Germanischer Lloyd (1997)
KEMA 01ATEX1024X Eex nA II T4
EMC marine applications - noise transmission gem. Germanischer Lloyd (1997)
Conformity marking CE
Cross section from [mm²] 0.08 mm²
Cross section to [mm²] 2.5 mm²
Cross section from [AWG] 28 AWG
Cross section to [AWG] 14 AWG
Voltage CSA 24 V
Weight 38.232 g
Color light gray
Height 64 mm
Height 2.52 in
Width 12 mm
Width 0.472 in
Depth 100 mm
Depth 3.937 in
Strip length from 8 mm
Strip length to 9 mm
Strip length 0.33 in