Connex-Electronics.com
Wago
Wago IO System - Analog Input Modules

Wago Analog Input Modules
Wago 750-472
Part Number Conformity Marking Approvals
Add part number 750-472 to your Quote. 750-472 CE cULus,
ABS, BV, DNV,
GL, LR, RINA,
cULus-EX,
KEMA
Data format for S5 control with FB 250:
Add part number 750-472/000-200 to your Quote. 750-472/000-200
16 bit single-ended 60 Hz :
Add part number 750-472/005-000 to your Quote. 750-472/005-000
2-CHANNEL ANALOG INPUT MOUDLE 0-20 mA CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION
The analog input module is able to provide power to the field device, receive the transmitted analog signals, and with electrical isolation, transmit them to the fieldbus. The 24 V supply is derived from the power jumper con-tacts. The shield (screen) is directly connected to the DIN rail. At approx. 25 mA the overload protection switches the measurement input to a high resistance state. Under normal operating conditions it is automatically switched back. This input module can supply the voltage for 2-conductor transducers.
Technical Information
Characteristic Value
No. of inputs 2
Voltage supply via system voltage DC / DC
CURRENT CONSUMPTION (INTERNAL) mA 75 mA
Input voltage non-linear, overload-protected; U = 1.2V + 160 Ohm x I mess
Signal current 0 - 20 mA
Input voltage max. (V) 24 V
Input resistance < 220 Ohm/ 20 mA
Overvoltage protection 30 V polarity reversal protection
Resolution (Bit) 15 Bit
Conversion time (typ) 80 ms
Measuring error (25°) < +/- 0.1 % of the full scale value
Temperature coefficient < +/- 0.01 % / K of the full scale value
Isolation 500 V system / supply
Data size 2 x 16 Bit Data2 x 8 Bit control / status (optional)
Input filter (Hz) 50 Hz
Noise rejection at sampling frequency < -100 dB
Noise rejection above sampling frequency < -40 dB
Operating temperature 0 °C ... + 55 °C
Storage temperature -25 °C ... +85 °C
Relative air humidity 95%
Vibration resistance acc. IEC 60068-2-6
Shock resistance acc. IEC 60068-2-27
Characteristic Value
Degree of protection IP 20
EMC immunity to interference acc. EN 50082-2 (96)
EMC emission of interference per EN 50081-1 (93)
UL 508 E175199, UL 508
EMC marine applications - noise proof gem. Germanischer Lloyd (1997)
Conformity marking CE
EMC marine applications - noise transmission gem. Germanischer Lloyd (1997)
Cross section from [mm²] 0.08 mm²
Cross section to [mm²] 2.5 mm²
Cross section from [AWG] 28 AWG
Cross section to [AWG] 14 AWG
Voltage CSA 24 V
Weight 55.5 g
Color light gray
Height 64 mm
Height 2.52 in
Width 12 mm
Width 0.472 in
Depth 100 mm
Depth 3.937 in
Strip length from 8 mm
Strip length to 9 mm
Strip length 0.33 in