Wago Analog Input Modules |
|
Part Number |
Conformity Marking |
Approvals |
750-472 |
|
cULus, ABS, BV, DNV, GL, LR, RINA, cULus-EX, KEMA |
Data format for S5 control with FB 250: |
750-472/000-200 |
16 bit single-ended 60 Hz : |
750-472/005-000 |
|
2-CHANNEL ANALOG INPUT MOUDLE 0-20 mA CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The analog input module is able to provide power to the field device, receive the transmitted analog signals, and with electrical isolation, transmit them to the fieldbus. The 24 V supply is derived from the power jumper con-tacts. The shield (screen) is directly connected to the DIN rail. At approx. 25 mA the overload protection switches the measurement input to a high resistance state. Under normal operating conditions it is automatically switched back. This input module can supply the voltage for 2-conductor transducers. |
|
Technical Information |
Characteristic |
Value |
No. of inputs |
2 |
Voltage supply |
via system voltage DC / DC |
CURRENT CONSUMPTION (INTERNAL) mA |
75 mA |
Input voltage |
non-linear, overload-protected; U = 1.2V + 160 Ohm x I mess |
Signal current |
0 - 20 mA |
Input voltage max. (V) |
24 V |
Input resistance |
< 220 Ohm/ 20 mA |
Overvoltage protection |
30 V polarity reversal protection |
Resolution (Bit) |
15 Bit |
Conversion time (typ) |
80 ms |
Measuring error (25°) |
< +/- 0.1 % of the full scale value |
Temperature coefficient |
< +/- 0.01 % / K of the full scale value |
Isolation |
500 V system / supply |
Data size |
2 x 16 Bit Data2 x 8 Bit control / status (optional) |
Input filter (Hz) |
50 Hz |
Noise rejection at sampling frequency |
< -100 dB |
Noise rejection above sampling frequency |
< -40 dB |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
|
Characteristic |
Value |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
per EN 50081-1 (93) |
UL 508 |
E175199, UL 508 |
EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
Conformity marking |
CE |
EMC marine applications - noise transmission |
gem. Germanischer Lloyd (1997) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Voltage CSA |
24 V |
Weight |
55.5 g |
Color |
light gray |
Height |
64 mm |
Height |
2.52 in |
Width |
12 mm |
Width |
0.472 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|