Wago Analog Input Modules |
|
Part Number |
Conformity Marking |
Approvals |
750-460 |
|
cULus |
4-CHANNEL ANALOG INPUT MOUDLE PT 100 / RTD CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The RTD (resistive temperature device) input module allows the direct connection of Pt or Ni resistance sensors. Only 2-conductor sensors can be connected. The module linearizes the entire temperature range automatically. A sensor error is indicated by a red LED. |
|
Technical Information |
Characteristic |
Value |
Temperature range |
-200 °C ... + 850 °C (Pt) -60 °C ... +250 °C (Ni) |
No. of inputs |
4 |
Current consumption (mA) |
65 mA |
Sensor types |
PT 100 (FACTORY PRESET), PT 200, PT 500, PT 1000, NI 100, RESISTANCE MEASURING |
Measuring current typ. |
0.5 mA |
Sensor connection |
2-conductor |
Resolution (over the complete area) |
0,1 °C |
Measuring error (25°) |
< +/- 0,1 °C |
Conversion time |
on request |
UL 508 |
E175199, UL 508 |
Conformity marking |
CE |
Voltage supply |
via system voltage DC / DC |
Isolation |
400 V system / supply |
Data size |
4 x 16 Bit data ;4 x 8 Bit controller / status (optional) |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
|
Characteristic |
Value |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
per EN 50081-1 (93) |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Weight |
55 g |
Color |
light gray |
Height |
64 mm |
Height |
2.52 in |
Width |
12 mm |
Width |
0.472 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|