Wago System Modules |
|
Part Number |
Conformity Marking |
750-628 |
|
MODULE BUS EXTENSION, COUPLER MODULE |
The internal data bus extension coupler module
750-628 replaces the fieldbus coupler/ controller on an I/O module assembly. It is the counterpart to the end extension module
750-627 . The connecting cable is plugged into the RJ 45 input socket, providing the logical connection to the fieldus coupler/ controller via the internal data bus extension end module
750-627 . The extension does not interfere with the fieldbus coupler/ controller, all bus module system functions remain unchanged. The RJ 45 output socket allows further extension of the system (max. 10 stations). The supply voltage for the field side and the internal electronics can be input separately. Both levels are electrically isolated from each other. Two diagnostic LEDs give information about the supply voltage for both the internal and field side. Two LEDs in the RJ 45 socket indicate fault-free communication with the bus coupler. The extension module can be used as the last coupler module in the system (switch on matching resistor) or as a bridge between two I/O module assemblies.
Installation Notes: In order to guarantee safe operating conditions when using the internal data bus extension modules 750-627/-628, the buscouplers must have the internal parameters set accordingly. Please order the WAGO extension setting tool
759-314 and use it to inform the buscouplers/ controllers
750-304
750-306
750-310
750-319
750-324
750-333
750-337 750-339,
750-342
750-804
750-806 750-19,
750-833
750-837
750-841
750-842 including all variations, of the new operating parameters. Please complete the manufacturing number matrix on the right-hand side of the couplers when updating the firmware and internal operating parameters. On the left-hand side of the buscouplers, please use the markers (enclosed in
759-314 to identify the modules that have been activated / deactivated. |
|
Technical Information |
Characteristic |
Value |
Max. no. of I/O bus modules |
64 (IN THE WHOLE SYSTEM) |
Distance between end module and coupler or coupler and coupler |
max. 5 m |
Transmission medium |
SHIELDED COPPER WIRE (ETHERNET PATCH CABLE) 4 x 2 x 0.25 MM², TWISTED PAIR, DOUBLE SHIELDING |
Buscoupler connection |
2 x RJ 45 SOCKET (INPUT + OUTPUT) |
Voltage supply |
DC 24 V (-15% / + 20%) |
Start-up current |
2.5 x CONTINUOUS CURRENT |
Input current (max) |
200 mA |
Efficiency of the power supply |
76% |
Internal current consumption |
150 mA |
Total current for the I/O modules |
400 mA |
Voltage via power jumper contacts (max) |
DC 24 V (-15% / + 20%) |
Current via power jumper contacts (max) |
DC 10 A |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
|
Characteristic |
Value |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
per EN 50081-1 (93) |
Conformity marking |
CE |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Weight |
74.5 g |
Color |
light gray |
Height |
65 mm |
Height |
2.56 in |
Width |
25 mm |
Width |
0.984 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
0 mm |
Strip length |
0.33 in |
Strip length to |
0 mm |
|
|