Wago System Modules |
|
Part Number |
Conformity Marking |
Approvals |
750-611 |
|
cULus, ABS, BV, DNV, GL, LR, RINA, cULus-EX, KEMA |
SUPPLY MODULE WITH FUSE HOLDER / DIAGN. CARRIER RAIL DIN 35 CAGE CLAMP CONNECTION |
The supply module provides field side power through the power jumper contacts. Maximum available supply current to all connected modules is 6.3 A. Should higher currents be necessary, intermediate supply modules must be added in the assembly. Supply modules may also be used to change the supply voltage to certain I/O modules within the assembly - on one fieldbus. This module is fuse-protected (size 5 x 20 mm). A blown fuse and the status of the supply voltage are indicated via LEDs. The fuse can be changed quickly, with ease, from the retractable fuse carrier. The module sends informa-tion about the status of the supply module to the fieldbus coupler through two input bits. One bit is for the status of the fuse. The other bit is for the status of the supply voltage. |
|
Technical Information |
Characteristic |
Value |
Voltage supply via power jumper contacts (max) |
AC 230 V |
Current via power jumper contacts (max) |
DC 6.3 A |
Current consumption (mA) |
5 mA |
Supply voltage detection level on |
> AC 164 V |
Supply voltage detection level off |
< AC 40 V |
Fuse |
5 x 20; T 6, 3 A |
Internal data width (Bit) |
2 Bit |
Operating temperature |
0 °C ... + 55 °C |
Storage temperature |
-25 °C ... +85 °C |
Relative air humidity |
95% |
Vibration resistance |
acc. IEC 60068-2-6 |
Shock resistance |
acc. IEC 60068-2-27 |
Degree of protection |
IP 20 |
EMC immunity to interference |
acc. EN 50082-2 (96) |
EMC emission of interference |
per EN 50081-1 (93) |
UL 508 |
E175199, UL 508 |
EMC marine applications - noise proof |
gem. Germanischer Lloyd (1997) |
UL 1604 |
E198726, UL 1604 Class 1 Dev2 ABCD T4A |
|
Characteristic |
Value |
EMC marine applications - noise transmission |
gem. Germanischer Lloyd (1997) |
KEMA |
01ATEX1024X Eex nA II T4 |
Conformity marking |
CE |
Cross section from [mm²] |
0.08 mm² |
Cross section to [mm²] |
2.5 mm² |
Cross section from [AWG] |
28 AWG |
Cross section to [AWG] |
14 AWG |
Voltage CSA |
230 V |
Current rating CSA |
10:00 AM |
Weight |
12.136 g |
Color |
light gray |
Height |
64 mm |
Height |
2.52 in |
Width |
12 mm |
Width |
0.472 in |
Depth |
100 mm |
Depth |
3.937 in |
Strip length from |
8 mm |
Strip length to |
9 mm |
Strip length |
0.33 in |
|
|