CP SNT 55W 5V 3A |
Representative Photo |
|
Technical Information |
|
Power Supply Type |
|
Switchmode |
Input Voltage |
|
85...265 VAC
/ 120...300 VDC |
Output Voltage |
|
5 VDC |
Output Current Rating |
|
3 A |
Housing Type |
|
CP |
Additional Data |
|
Rail Type |
|
35 mm
DIN-rail |
Input Voltage,
Minimum |
|
85 VAC / 120
VDC |
Input Voltage,
Typical |
|
115/230 VAC
±10%, 50/60Hz |
Input Voltage,
Maximum |
|
265 VAC / 300
VDC |
Input
Voltage/Current at 120 VAC |
|
1.10 A RMS
(±20%) |
Input
Voltage/Current at 230 VAC |
|
0.55 A RMS
(±20%) |
Input
Voltage/Current at 125 VDC |
|
590 mA
(±20%) |
Input
Voltage/Current at 250 VDC |
|
315 mA
(±20%) |
Frequency |
|
50/60 Hz
|
In-Rush
Current Protection |
|
Thermistor |
Overvoltage
Protection |
|
Varistor
|
Fuse |
|
2 A slow
fuse (internal) |
Switching
Frequency |
|
100 kHz
PWM |
Efficiency (at
Maximum Load) |
|
80%
|
Maximum
Ripple |
|
<50 mV
RMS |
Status
Indicator |
|
Green, power
on |
Output Current
(Max) |
|
3 A |
Maximum
Capacitive Load |
|
10,000
µF |
Load Share |
|
No |
Load (10-100%
Load) |
|
0.01
|
85 VAC to 265
VAC Line |
|
0.008
|
Overload
Protection |
|
Overcurrent
shutdown with automatic restart plus thermal shutdown short circuit |
Dielectric
Strength Input to Output |
|
3 kV RMS
|
Dielectric
Strength I/O to DIN-Rail |
|
3 kV RMS
|
Dielectric
Strength Input to Ground |
|
1.5 kV RMS
|
Dielectric
Strength Output to Ground |
|
500 V
RMS |
Storage
Temperature Range |
|
-40°C...+85°C |
Operating
Temperature Range |
|
-20°C...+50°C full rated load |
Wire Size |
|
#26...12
AWG 0.1...4.0 mm² |
Mechanical
Dimensions (LxWxH) mm (in.) |
|
98/57/131
(3.86/2.24/5.16) |
Certifications |
|
UL 508 listed,
CSA, CE |
Suggested Accessories
|
|
Chassis mounting kit:
7920560000
|
|