Port Variants |
Model Type |
Operating Temp. |
Order Number |
8 x RJ45 |
IE-SW-PL08M-8TX |
0 to +60°C |
1241040000 |
6 x RJ45, 2 x SC-Multimode |
IE-SW-PL08M-6TX-2SC |
0 to +60°C |
1241070000 |
6 x RJ45, 2 x ST-Multimode |
IE-SW-PL08M-6TX-2ST |
0 to +60°C |
1241080000 |
6 x RJ45, 2 x SC-Singlemode |
IE-SW-PL08M-6TX-2SCS |
0 to +60°C |
1241090000 |
16 x RJ45 |
IE-SW-PL16M-16TX |
0 to +60°C |
1241100000 |
14 x RJ45, 2 x SC-Multimode |
IE-SE-PL16M-14TX-2SC |
0 to +60°C |
1241120000 |
14 x RJ45, 2 x ST-Multimode |
IE-SW-PL16M-14TX-2ST |
0 to +60°C |
1241130000 |
Technology |
Standards |
IEEE 802.3 for 10BaseT IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3x for Flow Control IEEE 802.1D for Spanning Tree Protocol IEEE 802.1w for Rapid STP IEEE 802.1p for Class of Service IEEE 802.1Q for VLAN Tagging IEEE 802.1X for Authentication IEEE 802.3ad for Port Trunk with LACP |
Protocols |
IGMPv1/v2, GVRP, SNMPv1/v2c/v3, DHCP Server/Client, TFTP, SNTP, SMTP, RARP, GMRP, LACP, RMON, HTTP, HTTPS, Telnet, Syslog, DHCP Option 66/67/82, BootP, SSH, SNMP Inform, LLDP, Modbus/TCP, IPv6, IEEE 1588 PTP |
MIB |
MIB-ll, Ethernet-Like MIB, P-BRIDGE MIB, Q-Bridge MIB, Bridge MIB, RSTP MIB, RMON MIB Group 1,2,3,9 |
Flow Control |
IEEE 802.3x flow control, back pressure flow control |
Switch Properties |
Priority Queues |
4 |
Max. Number of Available VLANs |
64 |
VLAN ID Range |
VID 1 to 4094 |
IGMP Groups |
256 |
MAC Table Size |
8K |
Packet Buffer Size |
1 Mbit (IE-SW-PL08M) 2 Mbit (IE-SW-PL16M) |
Interface |
Fiber Ports |
100BaseFX ports (SC/ST connector) |
RJ45 Ports |
10/100BaseT(X) auto negotiation speed, Full/Half duplex mode, and auto MDI/MDI-X connection |
Console Port |
RS-232 (RJ45 connector) |
DIP Switches |
Turbo Ring, Master, Coupler, Reserve |
LED Indicators |
PWR1, PWR2, FAULT, MSTR/HEAD, CPLR/TAIL, 10/100M |
Alarm Contact |
2 relay outputs with current carrying capacity of 1A @ 24VDC |
Digital Inputs |
2 inputs with the same ground, electrically isolated
- +13 to +30 V for state "1"
- -30 to +3 V for state "0"
- Max. input current: 8mA
|
Optical Fiber |
|
100BaseFX |
Multi-mode |
Single-mode |
Wavelength |
1300nm |
1310nm |
Max. TX |
-10 dBm |
0 dBm |
Min. TX |
-20 dBm |
-5dBm |
RX Sensitivity |
-32 dBm |
-34 dBm |
Link Budget |
12 dB |
29 dB |
Typical Distance |
5 km (50/125µm multimode cable 4 km (62.5/125 µm multimode cable |
40 km (9/125 µm singlemode cable) |
Saturation |
-6 dBm |
-3 dBm |
|
Power Requirements |
Input Voltage |
24 VDC (12 to 45 VDC), redundant dual inputs |
Input Current |
IE-SW-PL08M-8TX: 0.26 A @ 24V IE-SW-PL08M-6TX-2SC/ST/2SCS: 0.36 A @ 24V IE-SW-PL16M-16TX: 0.41 A @ 24V IE-SW-PL16M-14TX-2SC/ST: 0.51 A @ 24V |
Overload Current Protection |
Present |
Connection |
2 removable 6-contact terminal blocks |
Reverse Polarity Protection |
Present |
Physical Characteristics |
Housing |
Metal, IP30 protection |
Dimensions |
IE-SW-PL08M: 80.2x135x105mm IE-SW-PL16M: 94x135x142.7mm |
Weight |
IE-SW-PL08M: 1040g IE-SW-PL16M: 1586g |
Installation |
DIN-Rail mounting |
Environmental Limits |
Operating Temperature |
0 to 60°C (32 to 140°F) |
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
Regulatory Approvals |
Safety |
UL508, UL60950-1, CSA C22.2 No. 60950-1, EN60950-1 |
Hazardous Location |
UL/cUL Class 1, Division 2, Groups A,B.C, and D; ATEX Zone 2, Ex nC llC |
EMI |
FCC Part 15, CISPR (EN55022) class A |
EMS |
EN61000-4-2 (ESD): IE-SW-PL08M...Series: level 3 EN61000-4-2 (ESD): IE-SW-PL16M...Series: level 2 EN61000-4-3 (RS), level 3; EN61000-4-4 (EFT), level 2; EN61000-4-5 (Surge), level 3; EN61000-4-6 (CS), level 3; EN61000-4-8 |
Maritime |
DNV, GL |
Shock |
IEC 60068-2-27 |
Freefall |
IEC 60068-2-32 |
Vibration |
IEC 60068-2-6 |
MTBF (meantime between failures) |
Time |
IE-SW-PL08M-...Series: 339,000 hours IE-SW-PL16M...Series: 247,000 hours |
Database |
Telcordia (Bellcore), GB |
Warranty |
Warranty Period |